6.3 PROFIBUS-specic Parameter List
Parameter Default value Range Conversion index Data type
Parameter 8-01 Control Site [0] Dig. & ctrl. word [0–2] – Uint8
Parameter 8-02 Control Word Source [0] FC RS485 [0–4] – Uint8
Parameter 8-03 Control Word Timeout Time 1 0.1–18000 -1 Uint32
Parameter 8-04 Control Word Timeout Function [0] O [0–10] – Uint8
Parameter 8-05 End-of-Timeout Function [0] Hold set-up [0–1] – Uint8
Parameter 8-06 Reset Control Word Timeout [0] Do not reset [0–1] – Uint8
Parameter 8-07 Diagnosis Trigger [0] Disable [0–3] – Uint8
Parameter 8-10 Control Word Prole [0] FC prole [0–x] – Uint8
Parameter 8-50 Coasting Select *[3] Logic OR [0–3] – Uint8
Parameter 8-51 Quick Stop Select *[3] Logic OR [0–3] – Uint8
Parameter 8-52 DC Brake Select *[3] Logic OR [0–3] – Uint8
Parameter 8-53 Start Select *[3] Logic OR [0–3] – Uint8
Parameter 8-54 Reversing Select *[3] Logic OR [0–3] – Uint8
Parameter 8-55 Set-up Select *[3] Logic OR [0–3] – Uint8
Parameter 8-56 Preset Reference Select *[3] Logic OR [0–3] – Uint8
Parameter 8-90 Bus Jog 1 Speed 100 RPM
0–
parameter 4-13
Motor Speed
High Limit [RPM] 67 Uint16
Parameter 8-91 Bus Jog 2 Speed 200 RPM
0–
parameter 4-13
Motor Speed
High Limit [RPM] 67 Uint16
Parameter 9-15 PCD Write Conguration – – – Uint16
Parameter 9-16 PCD Read Conguration – – – Uint16
Parameter 9-18 Node Address 126 1–126 0 Uint8
Parameter 9-22 Telegram Selection – [0–108] – Uint8
Parameter 9-23 Parameters for Signals – 0–573 – Uint16
Parameter 9-27 Parameter Edit [1] Enabled [0–1] – Uint16
Parameter 9-28 Process Control [1] Enable cyclic master [0–1] – Uint16
Parameter 9-44 Fault Message Counter 0 [0–8] 0 Uint16
Parameter 9-45 Fault Code 0 – – Uint16
Parameter 9-47 Fault Number 0 – – Uint16
Parameter 9-52 Fault Situation Counter 0 0–1000 0 Uint16
Parameter 9-53 Probus Warning Word 0 16 bits 0 V2
Parameter 9-63 Actual Baud Rate [255] No baud rate found 9.6–12000 kbits 0 Uint8
Parameter 9-64 Device Identication 0 [0–10] 0 Uint16
Parameter 9-65 Prole Number 0 8 bits 0 Uint8
Parameter 9-70 Edit Set-up [9] Active set-up [0–9] – Uint8
Parameter 9-71 Probus Save Data Values [0] O [0–2] – Uint8
Parameter 9-72 ProbusDriveReset [0] No action [0-2] – Uint8
Parameter 9-80 Dened Parameters (1) – 0–115 0 Uint16
Parameter 9-81 Dened Parameters (2) – 0–115 0 Uint16
Parameter 9-82 Dened Parameters (3) – 0–115 0 Uint16
Parameter 9-83 Dened Parameters (4) – 0–115 0 Uint16
Parameter 9-90 Changed Parameters (1) – 0–115 0 Uint16
Parameter 9-91 Changed Parameters (2) – 0–115 0 Uint16
Parameter 9-92 Changed Parameters (3) – 0–115 0 Uint16
Parameter 9-93 Changed Parameters (4) – 0–115 0 Uint16
Parameter 9-94 Changed Parameters (5) – 0–115 0 Uint16
Parameter 16-84 Comm. Option STW 0 0–FFFF 0 V2
Parameters
VLT
®
PROFIBUS DP MCA 101
46 Danfoss A/S © 01/2016 All rights reserved. MG37G202