51
APPENDIX 1
This document lists the event reporting codes for Ademco Contact ID reporting in the DL-300E. The event codes are
programmed by placing a number from 0-15 in the "100's" location of the communicator code for the event being
reported. The 10 's and 1's digit rogrammed are sent as the Zone Identifier. The following event codes will be sent for
the digit programmed:
PROGRAMMED 100's DIGIT ADEMCO EVENT CODE DEFINITION
0 122 Silent panic
1 110 Fire
2 120 Panic
3 130 Burglary
4 131 Perimeter Burglary
5 132 Interior Burglary
6 133 24 Hour Auxiliary
7 134 Entry/Exit Burglary
8 135 Day/Night Burglary
9 150 Non-burg 24 Hour
10 121 Duress
11 100 Medical Alarm
12 123 Audible Panic
If the following numbers are programmed for the contact ID event code, the event code will be made up of 3 alternate
programming locations according to the following:
PROGRAMMED 100's DIGIT PROGRAMMING LOCATIONS
13 365,366, 367
14 369, 370, 371
15 373, 374, 375
The following event codes are sent automatically but must be enabled by programming a 1 in the communicator code
location for that report:
REPORTING EVENT ADEMCO EVENT DIGIT LOCATIONS
Code pad Tamper 137 336
Autotest 602 340
Checksum Error 300 344
Opening/Closing 401 348 / 360
Cancel 406 354
A.C.Loss 301 356
Restore Event code for alarm 364
Zone Bypass 570 368
Zone Trouble 380 372
Low Battery 302 260
Battery Test Fail 309 360 / 255
Late to Close 404 592
Early to Open 400 588
Download Complete 410 596