Data Aire, Inc. DAP
TM
III BACnet Integration Instructions
Engineering Document - 600-000-460
Page 12 of 13
Object Name Instance
No. AV
Object Description Present-
Value
Writeable
Blower Runtime 21 The total runtime of the blower
motor(s) (Hour)
No
Condenser Runtime 22 The total runtime of the condenser.
This will be available when the
optional Relay module is installed
No
Dehumidification Runtime 23 The total runtime of dehumidification
No
Energy Saver Runtime
(Optional)
24 The total runtime of the energy saver
chilled water valve. This applies to
the DX unit with energy saver
cooling only.
No
Chilled Water Runtime 25 The total runtime of the chilled water
valve. This point applies to chilled
water unit only
No
Analog Output 1
(Optional)
37 Optional analog output 1 Value No
Analog Output 2
(Optional)
38 Optional analog output 2 Value No
Fire stat Temperature Limit 1001 Fire stat temperature limit setting
(100-150F) – Default 100 F
Yes-Real
value
High Humidity Limit 1002 High humidity alarm Limit setting
(10-90%). Default: 60 %
Yes- Real
value
High Temperature Limit 1003 High temperature alarm Limit setting
(50-90F). Default: 80 F
Yes- Real
value
Humidity Deadband 1004 Humidity deadband (0-15%).
Default: 3%
Yes- Real
value
Low Discharge Air Temperature
Limit (optional)
1005 Low Discharge Air temperature
alarm Limit setting (45-61F). This
requires an optional Discharge Air
temperature sensor. Default: 52 F
Yes- Real
value
Low Humidity Limit 1006 Low humidity alarm limit setting
(10-90%). Default: 40%
Yes- Real
value
Low Temperature Limit 1007 Low Return Air temperature alarm
Limit setting (50-90F). Default: 60F
Yes- Real
value
Chilled Water Available Limit
(Optional)
1008 Chilled Water available setpoint (40-
60F). Default: 50 F. This applies to
unit that has an energy saver or
auxiliary chilled water coil.
Yes- Real
value
Humidity Setpoint 1009 Humidity setpoint (30-70%).
Default: 50%
Yes- Real
value
Unit Start Delay 1010 Unit start time delay setting (5-600
seconds). Default: 5 seconds
Yes- Real
value
Temperature Deadband 1011 Temperature deadband (1-5F).
Default: 2F
Yes- Real
value
Temperature Setpoint 1012 Temperature setpoint (65-85F).
Default: 72F
Yes-Real
value
Fan Speed Control
(Optional)
1013 Optional fan speed control setting
(85-100%). Default: 100%. This
option requires an Analog module.
Yes- Real
value