Data Aire, Inc. DAP
TM
III BACnet Integration Instructions
Engineering Document - 600-000-460
Page 6 of 13
2.3.2 For the Ethernet connection, use the CAT-5 Ethernet cable. The DAP III panel
should be connected to the same network with the BMS by a network switch or a
network hub. Each unit requires having a dedicated IP address. Consult with
the building IT personnel or building network administrator on IP addressing.
3 Communication Port Setting
3.1 The RS-485 communication Port for BACnet MS/TP protocol is configured as
follow:
3.2 For BACnet IP communication UDP port setting, refer to the DAP III Operation
Manual for the procedure to enter an IP address and port setting to the DAP III.
The BACnet/IP UDP port (Listen port) in the DAP III is default to 47808.
Baud Rate
9600 (adjustable)
Word Length 8
Parity None
Stop Bits 1
Network switch or
hub (Supplied by
DAP III Display board of unit
#1 with Ethernet card
(Supplied by Data Aire.)
DAP III Display board of unit
#2 with Ethernet card
(Supplied by Data Aire.)
Ethernet connection to BMS
BMS