Data Aire, Inc. DAP
TM
III BACnet Integration Instructions
Engineering Document - 600-000-460
Page 7 of 13
4 BACnet Object Definitions
4.1 Binary Value Objects
4.1.1 Readable fields
Object-identifier Status-flags
Object-name Event-state
Object-type Out-of-service
Present-value
4.1.2 Object List
Object Name Instance
No. BV
Object Description Present-
Value
Writeable
Dehumidification 1 Unit is dehumidifying
No
Humidification 2 Unit is humidifying
No
Energy Saver 3 Energy Saver function is active
No
Cooling Held 4 Cooling is inhibited
No
Heating Held 5 Heating is inhibited
No
Humidification Held 6 Humidification is inhibited
No
Dehumidification Held 7 Dehumidification is inhibited
No
Reheat During Dehumidification 8 Reheat on during dehumidification
No
Water Under Floor 9 Water Under Floor detection alarm
No
No Air Flow 10 Loss of the air flow alarm
No
Dirty Filter 11 Filter clogged alarm
No
Humidifier Problem 12 Loss of the humidifier make-up water
pressure alarm
No
Low Voltage Warning 13 DC power of the DAP III boards drops
below the required level
No
Fire-Stat Trip 14 The return air temperature rises above
the Firestat temperature setting limit
No
Compressor Short Cycle Warning 15 Compressor short cycle warning is active
No
Power Problem 16 Power reset or unit restart notification
No
Humidity Sensor Problem 17 Faulty Humidity sensor detected
No