Data Aire, Inc. DAP
TM
III BACnet Integration Instructions
Engineering Document - 600-000-460
Page 13 of 13
4.4 Multi-State Value Objects
4.4.1 Readable fields
Object-identifier Status-flags
Object-name Event-state
Object-type Out-of-service
Present-value Number-of-states
4.4.2 Object List
Object Name Instance
# MSV
Object Description Present-
value
Writeable
Person To Contact
(Optional)
13 Information of the person to contact
on the alarm event. This requires a
factory-preprogrammed message.
No
Reset Mode Warning 14 Loss of power or Unit restart warning
message
No
Water Under Floor Alarm Action 17 Water under floor alarm action
setting, menu 4-9 of the DAP III
panel. This can be set to unit
shutdown or compressor lock-out
No
No Water Flow Alarm Action
(optional)
18 No water flow alarm action setting,
menu 4-10 of the DAP III panel. This
can be set to compressor lock-out or
none. This requires an optional water
flow sensor.
No
Energy saver Lockout Time
(optional)
19 Energy saver lockout time delay once
the DX cooling comes on. This is set
on menu 3-8 of the DAP III panel.
Energy saver option required
No
Auto flush Timer
(Optional)
1001 Auto flush Timer setting. This setting
only applies when an optional
Infrared humidifier is used.
Yes-
Unsigned
value
Unit on/off Control 1002 This point controls the unit on/off.
The default setting value is 1; unit is
ON. Changing the setting value to 2
will turn the unit OFF. Default =1
(ON).
Yes-
Unsigned
value
4.5 References
ANSI/ASHRAE Standard 135-2001, BACnet - A Data Communication Protocol
for Building Automation and Control Networks