Data Aire, Inc. DAP
TM
III BACnet Integration Instructions
Engineering Document - 600-000-460
Page 10 of 13
4.2 Analog Input Objects
4.2.1 Readable fields
Object-identifier Status-flags
Object-name Event-state
Object-type Out-of-service
Present-value Units
4.2.2 Object List
Object Name Instance
No. AI
Object Name Present-
Value
Writeable
Return Air Temperature 1 Current Return Air temperature
No
Relative Humidity 2 Current Relative humidity
No
Discharge Air Temperature 3 Current Discharge Air temperature. This
temperature is only available when an
optional Discharge Air sensor is installed
No
Chilled Water Temperature
(Optional)
4 Chilled Water temperature. This
temperature is only available when an
optional Chilled water sensor is installed.
No
Analog Input 1 Sensor
(Optional)
5 An optional analog sensors such as
temperature transmitter must be installed
and programmed into analog module
input 1
No
Analog Input 2 Sensor
(Optional)
6 An optional analog sensor such as
temperature transmitter must be installed
and programmed into analog module
input 2.
No
Analog Input 3 Sensor
(Optional)
7 An optional analog sensors such as
temperature transmitter must be installed
and programmed into analog module
input 3
No
Analog Input 4 Sensor
(Optional)
8 An optional analog sensors such as
temperature transmitter must be installed
and programmed into analog module
input 4
No
4.3 Analog Value Objects
4.3.1 Readable fields
Object-identifier Status-flags
Object-name Event-state
Object-type Out-of-service
Present-value Units