118
Alarm Screen
Description &
Classification
Possible Causes
Corrective Actions
C1 or C2 Low
Pressure
Circuit
pressure is
under 50 PSI
(it will cut- in at
90 PSI)
** Urgent
Not enough air flow
though evaporator coil
Low Indoor
Temperature
Dirty Filters
Low refrigerant charge
Inoperative Expansion
valve
Filter Drier clogged up
Restricted liquid line
Undersized lines
Inefficient Compressor
Incorrect settings of
digital input on the
controller
Blower motor on low speed or
failed motor, High static
pressure, or undersized plenums
Raise the temperature above
68°
degrees
Replace filters
Check sub-cooling, and test for
leaks. Repair leaks and add
refrigerant
Adjust and check valve
operation and replace if needed
Replace filter drier
Repair restriction
Check line design at IOM
Test compressor efficiency
Go to Menu L Configure I/O
and change the Low-Pressure
Switch action setting
C1 or C2 High
Pressure
Circuit
pressure is
over the
pressure
setting of the
switch
** Urgent
High outdoor ambient
temperature
Recirculating of
condensing air
Low heat rejection at
condenser
Not enough air across
Condenser coil
Excessive Airflow
across the evaporator
coil
Heavy Load
Wait until ambient temperature
drops
Remove obstruction to air flow
Check condenser fan motor
operations on air cooled, check
water flow on water cooled.
Check condenser fan cut-in
temperatures, and clean
condenser coil if needed
Check blower speed