EasyManua.ls Logo

Data Aire dap4 - Alarms Overview; Humidity and Heat Inhibition Alarms

Default Icon
137 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
119
Alarm Screen
Description &
Classification
Possible Causes
Corrective Actions
•
Return duct damaged
•
Sensing Bulb is loose
•
Over charge of
refrigerant
•
Expansion valve
Overfeed
•
Faulty high-pressure
switch. Cut out:
R410A at 575 PSI or
R407 at 450PSI.
•
High indoor temperature, check
blower speed, and check
equipment selection
•
Check return duct for leakage
and check temperature entering
evaporator coil
•
Tighten bulb bracket
•
Check sub-cooling (8-10) and
adjust charge if necessary.
Recover charge, evacuate, then
re-charge system
•
Adjust and check expansion
valve operations
•
Replace high pressure switch
Compressor
Short Cycle
Compressor
has started
more than 10
times in an
hour.
** Urgent
•
Not enough Heat Load
or Oversized System
•
Temperature Dead
Band is set too low
•
Humidity Dead Band
is too low (causing
frequent dehum
cycles).
•
No electric reheat
•
Lack of vapor barrier
•
Unusual high rate of
building heat gain
•
Check for heat load
•
Check and raise Temperature
Dead Band
•
Check and raise Humidity Dead
Band
•
Check reheat elements for
proper operation
•
Seal room with the proper vapor
barrier
•
Check room infiltration
Hi Humidity
The return air
humidity is
higher than the
high humidity
alarm limit.
*Warning
•
Humidity is too High
•
Humidity alarm set
point needs to be
adjusted
•
Check humidity in the room
•
Check High humidity alarm set
point (range 35%-90%)
•
Check water vapor infiltration