123
Alarm Screen
Description &
Classification
Possible Causes
Corrective Actions
**Urgent
•
Wiring problem
•
Bad Flow Switch
•
Incorrect settings of
digital input on the
controller
•
Check electrical wiring
•
Replace flow Switch
•
Go to Menu L- Configure I/O and
change the Water Flow Switch
action setting
Floor Water
Senses water
at the floor
Urgent/Critical
•
Water or moisture
detected on floor
•
Faulty or damaged
sensor
•
Faulty Water
Detection Module
•
Incorrect settings of
digital input on the
controller
•
Allow water or moisture to dry
and alarm will auto reset
•
Check for 10K resistance,
replace sensor if necessary
•
Check 24 volts at the Water
Detection Module
•
Go To I/O Input in Menu L Floor
Water Switch and change the
Action
Humidity
Inhibited
Humidification
mode is
prohibited from
running
*Warning
•
Optional alarm input
switch is configured to
inhibit humidifier
•
BMS command sent
•
Unit is in a Zone
Control network that
inhibits humidification
if any unit has recently
been dehumidifying
•
Check optional alarm settings
and inputs
•
Check BMS
•
Check Zone Control settings and
humidity set points of all units.
Heat Inhibited
Reheat mode
is prohibited
from running
*Warning
•
Optional alarm input
switch is configured to
inhibit reheat
•
BMS command sent
•
Unit is in a Zone
Control network that
inhibits humidification
if any unit has recently
been dehumidifying
•
Check optional alarm settings
and inputs
•
Check BMS
•
Check Zone Control settings and
temperature/humidity
set points
of all units