126
Alarm Screen
Description &
Classification
Possible Causes
Corrective Actions
External Temp.
Module Sensor
T** Low
Temperature
The optional
Rack sensor
has a High
Temp Alarm
*Warning
Temperature is below
rack sensor low alarm
set point
Faulty sensor
Check temperature of sensor
and set point for alarm
Check sensor and replace
sensor
External Temp.
Module Sensor
Failure
The optional
Rack sensor in
Fault Alarm
*Warning
Faulty Rack Sensor
Check the sensor indicated and
replace sensor if necessary.
Suction
Pressure/Temp
High Suction
Pressure of
Temperature
Compressor running
at minimal speed.
Heavy Load on
Evaporator.
Too much air flow
EEV failed Open
Faulty Sensor
Check input signal to
compressor speed control and
the compressors actual speed.
Check temperature set point and
compressors mode of operation
(Discharge or Return control)
Check fan speed control and set
point
Check EEV
EVD Failure
Electronic
Valve Driver
failure
Damaged EVD
EVD Sensors Failure
Refrigerant Charge
problem
Replace EVD
Check or replace sensors
Check refrigerant charge
Lost Phase
Phase failure
alarm when
optional power
meter installed
***Critical
Lost power on a phase
of the high voltage
supply. Unit will shut
down.
Check high voltage connections
to unit. Check power meter or
phase loss detector
High CO2
(gPOD units
only)
CO2 level is
higher than
alarm set point
**Urgent
CO2 level is too high
and may be
dangerous. Evacuate
anyone in the affected
area.
Check CO2 level in the air and
check the CO2 valve to make
sure it turns off completely.
Check CO2 setpoint