127
Alarm Screen
Description &
Classification
Possible Causes
Corrective Actions
Incorrect settings
Faulty Sensor
Out of calibration
Check CO2 Sensor
Calibrate sensor
Low CO2
CO2 level is
higher than
alarm set point
(gPOD units
only)
*Warning
Co2 level is lower than
normal
Incorrect settings
Faulty Sensor
Loose Connection
Out of calibration
Check Co2 Level
Check settings
Check Co2 Sensor
Check Connection and cable
Calibrate sensor
VFD Failure
VFD alarm
relay is
energized
**Urgent
VFD has an alarm
Low or High Pressure
alarm
Check VFDs display for alarm or
warning.
When a low or high pressure
alarm occurs it may cause the
VFD alarm to happen as well.
Resolve this by focusing on the
cause of the Low or High
pressure alarm.
Pump-Down
Exceeded
Maximum Time
or Count
Compressor
failed to Pump-
Down
**Urgent
Suction pressure
remained above
pump-down setpoint
or rose after being
pumped down.
Alarm requires
acknowledgement to
clear
Replace LLSV
Check Suction Pressure Sensor
Optional Alarm
AE Damper
Not Open
Damper end
switch did not
verify position
*Warning*
Damper modulation is
at maximum but end
of travel switch did not
close.
Check end switch closes when
damper is in open position
Check damper mechanical
operation
Optional Alarm
AE Damper
Not Closed
Damper end
switch did not
verify position
Damper modulation is
at minimum but end of
Check end switch closes when
damper is in closed position