EasyManua.ls Logo

Data Aire dap4 - Page 135

Default Icon
137 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
131
Dap4 Wiring Connections - continued
Analog Output (0-10V, 10mA)
Pin ID
Connector
Unit TB
Water Valve Control
(or HGRH valve if enabled)
Y1
J4-3
TB2-34
VG0
J4-2
TB2-35
Humidifier
Y2
J4-4
TB2-51
VG0
J4-2
TB2-52
Fan Speed
Y3
J4-5
TB4-1, 2
VG0
J4-2
TB4-3, 4
SCR heat
Y4
J4-6
VG0
J4-2
TB2-35
Variable Compressor
Y5
J20-1
VG0
J4-2
TB2-35
Damper for Airside Economizer
Y6
J20-2
VG0
J4-2
TB2-35
Temperature VS resistance table (Data Aire normal NTC only)
Deg. F
Kohm
Deg. F
Kohm
Deg. F
Kohm
Deg. F
Kohm
Deg. F
Kohm
32.00
27.28
51.80
17.24
71.60
11.20
91.40
7.45
111.20
5.08
33.80
26.13
53.60
16.55
73.40
10.78
93.20
7.19
113.00
4.91
35.60
25.03
55.40
15.90
75.20
10.38
95.00
6.94
114.80
4.74
37.40
23.99
57.20
15.28
77.00
10.00
96.80
6.69
116.60
4.59
39.20
22.99
59.00
14.68
78.80
9.63
98.60
6.46
118.40
4.44
41.00
22.05
60.80
14.12
80.60
9.28
100.40
6.24
120.20
4.30
42.80
21.15
62.60
13.57
82.40
8.94
102.20
6.03
122.00
4.16
44.60
20.29
64.40
13.06
84.20
8.62
104.00
5.82
123.80
4.02
46.40
19.40
66.20
12.56
86.00
8.31
105.80
5.63
125.60
3.90
48.20
18.70
68.00
12.09
87.80
8.01
107.60
5.43
127.40
3.77
50.00
17.96
69.80
11.63
89.60
7.72
109.40
5.25
129.20
3.65

Other manuals for Data Aire dap4