Reheat The type of reheat used. Choices are:
None - No reheat installed.
One - A single stage of heat (default on minidap4).
1-Elect - A single stage of reheat used only in dehumidification mode.
HW Valve - (Not shown on IRDX Model). A hot water valve is used for heating.
The valve is modulated using the SCR algorithm on Y4. Notice: A discharge air
temperature sensor must be installed to select this mode.
Two - (Not shown on IRDX Model or MiniDAP). Two stages of heat.
Three - (Not shown on IRDX Model or MiniDAP). Three stages of heat (default
on large dap4).
3-Elect - (Not shown on IRDX Model or MiniDAP). Three stages of reheat used
only in dehumidification mode.
HGRH - Hot Gas valve (analog output Y1) is modulated by a PID algorithm to
maintain temperature of the discharge air during dehumidification only.
HGRH+1 Like HGRH mode but has an additional electric heat output HT3
(DO11) that turns on when temperature drops below setpoint minus heat dead
band (when dehumidifying or not).
Dual HGRH Like HGRH mode but has a second HGRH coil for C2 (Y2).
Enable Rotation: (Only displayed when there is more than one stage of electric
reheat). Default setting is that FIFO rotation is enabled.
Lead Reheat: (Only displayed when rotation is enabled) indicates the current lead
reheat stage. You can also manually change which one is the lead.
Delay After DX: (Only displayed if DX is enabled). This delay prevents heating
from running right after a compressor finished cooling. Range of adjustment is 0 to
100 mins, with a default of 10 mins.
Enable SCR Y4: This enables the SCR modulation (Y4) for heat. Output Ht2 is
used to energize the SCR module.
SCR Band: (Only displayed when SCR is enabled). This setting determines how
far below set point minus dead band temperature can drop until the SCR
modulation will reach 100%. Range of adjustment is 1 to 20°F with a default of 1°F.