MENU J FACTORY SETTINGS (factory level) continued
W
a
t
e
r
V
a
l
v
e
S
e
tt
i
n
g
s
W
t
r
V
l
v
:
Engy Svg
C
oo
l
W
t
r
V
l
v
V
o
l
t
age
:
0
-
10
E
/
S
A
ss
i
s
t:
1
C
o
m
p
E
/
S
S
t
a
r
t
-
up
T
i
m
e
:
0
s
E
/
S
L
o
c
kou
t
T
i
m
e
:
5m
E
/
S
C
h
a
n
ge
ov
e
r
:
2
.
0
S
w
i
t
c
h
t
o
DX
0h
r
s
Wtr Vlv: The selection of the water valve function. Choices are:
None No chilled water valve used. (This is the default selection) Chill
Wtr Cool Uses chilled water to perform all cooling, without DX. Engy
Svg Cool Uses chilled water to cool (if it is cold enough) before
requiring compressors to assist.
Aux Chill Wtr Same energy saving as above but the chilled water source
is independent from DX condensing circuit; therefore, auxiliary condenser
contact (DO8) will not energize.
Chill Wtr Reg Like the Chill Wtr Cool, it uses chilled water to perform all
cooling. However, the discharge air is used for temperature control, so a
discharge air temperature sensor is required. (Note: discharge air is used
regardless of the Control Tempsetting).
Wtr Vlv Voltage: The signal voltage used for the installed water valve. Choices
are: 0-10, 2-10, 7-10, 6-9 and 4-7 volts.
Note: Selections below are only displayed in Engy Svg or Aux Chill Wtr modes.
E/S Assist: The number of compressors that may assist chilled water cooling
when in the E/S Available mode. Choices are: None, 1, 2 or 4 compressors. A
discharge temperature sensor is required. Note: All compressors may run when
not in the E/S Available mode.
E/S Startup Time: Allows flow of CW before causing a high temperature lockout in
energy saver modes. Range is 0 (default) to 300 seconds.
E/S Lockout Time: This is the time that energy saver will be disabled due to high
water temperature or E/S Changeover due to high air temperature. Range of time
is 1 to 60 minutes with a default of 15mins.
E/S Changeover: This feature locks out CW energy saver and switches totally to
DX cooling if the air temperature reaches setpoint + deadband + this setting. Once
locked out and the E/S Lockout timer has expired, temp must drop back to setpoint
for CW cooling to resume. Range is from Noneor 1 to 10 degrees with default of
2. When set to None, the energy saver will continue to run along with E/S assist

Other manuals for Data Aire dap4