DX Assist Delay: This setting delays the compressors from starting after
the CW valve is fully open. The CW valve must remain fully open for the
length of this delay. Once the compressor(s) have started, the CW valve
will be forced 100% open. Range of adjustment is 0 to 60 minutes with a
default of 2 mins.
DX -> CW Delay: When compressors have turned off, the CW valve will
continue to be fully open for the length of this delay before returning to
normal PID modulation. Range of adjustment is 0 to 60 minutes with a
default of 5 mins.