Data Aire dap4 - MENU K - ALARMS & LIMITS (Service Level); Alarm Settings Overview

Default Icon
137 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
59
MENU J FACTORY SETTINGS (factory level) continued
Damper Status: This line will indicate OK- Modulating” when the Airside
Economizer is available to perform cooling. Otherwise, it will state what condition is
preventing it from running.
Damper Modulation: Shows the current damper modulation based on
temperature demand.
Min Damper Open: This setting determines the minimum opening of the damper.
Range of selection is 0 to 70% with a default setting of 0%.
Max Damper Open: This setting determines the maximum opening of the damper.
Range of selection is 70% to 100% with a default setting of 100%.
R
ac
k
S
e
tt
i
n
g
s
T
e
m
p
S
e
n
s
o
r
s
U
s
e
d
:
32
G
r
oup
s
U
s
e
d
:
16
E
x
c
l
ud
e
T
B
a
nd
:
10
.
0
U
s
e
A
v
e
r
age
of
G
r
oup
s
A
v
g
:
H
i
g
h
e
s
t
3
G
r
oup
s
R
e
f
r
e
s
h
R
a
t
e
:
15
m
i
n
O
ffs
e
t
S
e
t
po
i
n
t:
N
o
Temp Sensors Used: Select how many rack sensors are installed. Range of
selection is 0 (default) to the maximum sensors supported by the module. Note: An
external rack sensor module is required when more than 1 sensor is selected (3
sensors on IRDX and IRCW models). Use the Options Installed screen to select
the type of external module installed.
Groups Used: (only shown when 4 or more temp sensors are installed). This is
the total number of groups that the sensors will be arranged in. Range of
adjustment is: None (default setting) to ½ the number of temp sensors installed.
When groups are not used, all sensors are effectively in the same group.
Exclude T Band: (only shown when external module is installed). This is the
amount of deviation from the average rack temperature. If a sensor deviates more
that this setting, it will be excluded from control and determining the average
temperature. Once it comes back within the exclude T band for at least 60
seconds, it will return to normal function. Range of adjustment is 5.0°F to 99.0°F
with a default setting of 10.0°F
Use Highest: The rack temperature can be determined by using the Highest or the
Average temperature of sensors or groups of sensors.