Damper Status: This line will indicate “OK- Modulating” when the Airside
Economizer is available to perform cooling. Otherwise, it will state what condition is
preventing it from running.
Damper Modulation: Shows the current damper modulation based on
temperature demand.
Min Damper Open: This setting determines the minimum opening of the damper.
Range of selection is 0 to 70% with a default setting of 0%.
Max Damper Open: This setting determines the maximum opening of the damper.
Range of selection is 70% to 100% with a default setting of 100%.
R
ac
k
S
e
tt
i
n
g
s
T
e
m
p
S
e
n
s
o
r
s
U
s
e
d
:
32
G
r
oup
s
U
s
e
d
:
16
E
x
c
l
ud
e
T
B
a
nd
:
10
.
0
U
s
e
A
v
e
r
age
of
G
r
oup
s
A
v
g
:
H
i
g
h
e
s
t
3
G
r
oup
s
R
e
f
r
e
s
h
R
a
t
e
:
15
m
i
n
O
ffs
e
t
S
e
t
po
i
n
t:
N
o
Temp Sensors Used: Select how many rack sensors are installed. Range of
selection is 0 (default) to the maximum sensors supported by the module. Note: An
external rack sensor module is required when more than 1 sensor is selected (3
sensors on IRDX and IRCW models). Use the Options Installed screen to select
the type of external module installed.
Groups Used: (only shown when 4 or more temp sensors are installed). This is
the total number of groups that the sensors will be arranged in. Range of
adjustment is: None (default setting) to ½ the number of temp sensors installed.
When groups are not used, all sensors are effectively in the same group.
Exclude T Band: (only shown when external module is installed). This is the
amount of deviation from the average rack temperature. If a sensor deviates more
that this setting, it will be excluded from control and determining the average
temperature. Once it comes back within the exclude T band for at least 60
seconds, it will return to normal function. Range of adjustment is 5.0°F to 99.0°F
with a default setting of 10.0°F
Use Highest: The rack temperature can be determined by using the Highest or the
Average temperature of sensors or groups of sensors.