No Water Flow Action: The water flow alarm cannot be disabled and is checked
only when there is a need for DX cooling or if the CW valve has opened at least
60%. This setting determines what should happen when the alarm occurs. (Note: a
flow sensor required).
Alarm Only: (Default) The alarm will not cause any change in operation.
Turn Compressors Off: The compressors will be shut down and kept off
for 5 minutes after the water flow alarm is no longer active. A countdown
showing the time remaining until the compressors will be allowed to run is
shown on the no water flow alarm screen.
Lockout CW: The CW cooling will be locked out for ES Lockout Time
before CW cooling will be allowed to function again. A countdown showing
the time remaining until CW will be allowed to run is shown on the no water
flow alarm screen.
Lockout Both CW & DX: Operates as the CW lockout does but
compressors will also be lockout along with the CW being locked out.
Wtr Flow Alm Dly: This is the amount of time that the water flow alarm is
delayed from occurring. The selection is from 5 to 180 seconds with a
default of 5 seconds.
No Air Flow: The air flow alarm cannot be disabled and is checked when the fan
is on. The alarm is delayed for about a minute when the system is initially turned
on.
Air Flow Alm Dly: This is the amount of time that the air flow alarm is
delayed from occurring. The selection is from 5 to 180 seconds with a
default of 5 seconds.