MENU K ALARMS & LIMITS (Service Level) continued
Hi Temp Alarm: When the temperature of any rack sensor rises above the alarm
set point, a high rack temperature alarm will occur. This alarm is a warning only.
The range of set point adjustment is 70 to 90°F with a default setting of 90°F.
Lo Temp Alarm: When the temperature of any rack sensor drops below the alarm
set point, a low rack temperature alarm will occur. This alarm is a warning only.
The range of set point adjustment is 50 to 90°F with a default setting of 50°F.
D
i
s
c
h
a
r
ge
T
e
m
p
A
l
a
r
m
s
Low
D
i
s
c
h
T
e
m
p
A
l
m
:
Y
e
s
S
hu
t
O
ff
C
o
m
p
s
:
Y
e
s
S
e
t
po
i
n
t:
45
H
i
D
i
s
c
h
T
e
m
p
A
l
m
:
Y
e
s
S
e
t
po
i
n
t:
85
D
e
l
a
y
:
60
s
The Discharge Temp Alarm screen will only appear if a Discharge Temperature
sensor is enabled in the I/O Config menu.
Low Disch Temp Alm: When enabled the alarm will occur when the temperature
drops below the setpoint. The default setting is No(disabled)
Shut Off Comps: When set to Yes (default) the low discharge temp alarm
will cause the compressors to turn off. Otherwise, the alarm is only a
notification.
Setpoint: The range is 40 to 60°F with a default setting of 45°F.
Hi Disch Temp Alm: When enabled the alarm will occur when the temperature
exceeds the setpoint when unit is cooling. The default setting is “No(disabled)
Setpoint: The range is 65 to 100°F with a default setting of 85°F.
Delay: Time that alarm is delayed so that cooling function can bring temp
below the alarm setpoint. The range of adjustment is 30 to 180 seconds with
a default setting of 60 seconds.