This Alarm screen will only appear if the CW Energy saver is enabled.
High Temp Alarm: When enabled (default), the alarm will occur when the
temperature of the water rises above the Energy Saver Setpoint and is no longer
able to cool. The alarm will clear when CW temp drops below the setpoint and
deadband. (These thresholds are in the Setpoints menu)
Delay of Hi Temp: The amount of time that water temperature must remain above
the E/S setpoint high before lockout occurs. The range of adjustment is 5 to 300
seconds with a default of 30 seconds.
H
u
m
i
d
i
t
y
A
l
a
r
m
s
H
i
H
u
m
i
d
i
t
y
A
l
a
r
m
:
Y
e
s
S
e
t
po
i
n
t:
60
%
•
Lo
H
u
m
i
d
i
t
y
A
l
a
r
m
:
Y
e
s
S
e
t
po
i
n
t:
40
%
Hi Humidity Alarm: When set to “Yes” (default) the alarm is enabled. When the
return air relative humidity rises above the alarm set point, a high humidity alarm
will occur. During this alarm, the humidifier will be disabled. The range of set point
adjustment is 35 to 90% with a default setting of 60%.
Lo Humidity Alarm: When set to “Yes” (default) the alarm is enabled. When the
return air relative humidity drops below the alarm set point, a low humidity alarm
will occur. The range of set point adjustment is 10 to 65% with a default setting of
40%.