Zone Control
Temperature Assist: Yes
ES Before DX: Yes
Tmp Assist Band: 1.5
Engy DX DBand: 1.3
Standby On Delay: 30s
Standby Off Delay: 900s
Enable Inhibit: Yes
Temperature Assist – If set to “Yes”, additional standby units will be
requested to come on when the average zone temperature is higher than
the cooling set point plus dead band plus 1.5°F.
ES Before DX: If set to “Yes”, the units in the zone will run in CW Energy
Saver mode prior switching to DX cooling.
Tmp Assist Band: (only shown when ES Before DX is enabled). Offers an
adjustable band of 1.0 to 10.0 degrees (default of 1.5) instead of the fixed
1.5°F for temperature assist.
Engy DX Band: (only shown when ES Before DX is enabled). Offers an
adjustable band of 1.3 to 10.0 degrees (default of 1.3) instead of the fixed
1.3°F threshold that is added to DX staging when energy saver is running.
Standby On Delay – This is how long Unit 1 will wait before requesting a
standby unit to turn on. The range of adjustment is 30 to 999 seconds, with
a default setting of 30 seconds.
Standby Off Delay – This is how long Unit1 will wait before allowing an
assisting unit to return to standby. The range of adjustment is 30 to 999
seconds, with a default of 900 seconds. Note: although an assisting unit
may be allowed to return to standby after this delay has expired, the unit
may continue to run if the “Finish Run->Stdby” selection is set to “Yes”.
Enable Inhibit – If set to “Yes” (the default and recommended setting), the
Zone Control will prevent units from performing conflicting operations. For
example: If any unit is cooling, others will be prevented from heating, or if
any unit is dehumidifying, other will be prevented from humidification.