84
MENU M Set Zone Control (continued)
Zone Control
Rotation: Day & Time
Every Day at: 4:00AM
Force Rotation: No
Rotation: To even out runtime among standby units, a scheduled rotation
of the lead unit may be chosen. The available selections are:
None (Default) Rotation is disabled and the lead unit will not change.
The lead unit selection will appear instead of the rotation timing
selections below.
Day & Time This selection will display an additional selection for the
Day (Everyday or Sunday through Saturday) and the time when rotation
will occur. The time is in AM/PM format.
Every X” Hrs - Rotation will occur at the selected time increment
beginning from when the increment is selected. It is not based on the
clock hour status. Range is 1 to 48 Hrs
Exercise U2 (Only shown when two units are installed). This setting is
used for applications when unit 2 is a backup unit” and unit 1 is normally
doing all the cooling. This function sets how long the rotation to unit 2
will last before going back to unit 1. When Exercise U2is selected, the
bottom line sets how many hours unit 2 will be allowed to run. Range of
adjustment is 1 to 24 hours with a default setting of 1 hour.
Force Rotation (Only shown when rotation is enabled and not selected
as Exercise U2). This selection appears when rotation is enabled and
allows you to manually cause a rotation. The timed rotation will still occur as
expected and does not get reset when force rotation is used.