Date – Choose the day and month of the special day.
Setting – Choose which schedule will run during the special day.
When the clock reaches the selected special day (at 12:00 midnight) the
schedule that is selected for this day will run. When the clock reaches the
end of this day (at 12:00 midnight) the special day schedule will end, and the
normal weekday schedule will take over. When (------) is shown, no special
day schedule is set.
Zone Alarm Function 1
Stby Off
CW Sensor No No
This screen (one of 6) will only appear on Unit #1.
The Zone Alarm screens allow all units in the zone to report selected alarms
to Unit 1. Based on the alarm selection, Unit 1 will act as described below.
There are up to 35 types of alarms that can be chosen. Only the “DX Off by
Alm” Stby setting is defaulted to “Yes”.
Standby (Stby): When the selected alarm occurs in the unit, the Zone
Control temporarily activates a standby unit to supplement the unit in
alarm.
Off: As in standby alarms described above; when the selected alarm
occurs in the unit, the Zone Control activates a standby unit to
supplement the unit that had the alarm. In addition; Unit 1 will
reconfigure the unit as Off (for both Primary and Secondary schedules)
so that it will no longer be allowed to run. Once a unit is reconfigured to
be Off, the unit must be set back to standby on Unit 1 in order to resume
operation.
However, if all standby units are already running (none left in standby),
the unit will be allowed to continue running.