DKG-325 User Manual Firmware V-56
- 32 -
The parameters below define the function of the auxiliary relay output. The relay function is selected
from below list.
Program Group: Relay Definitions
PGM
Parameter Definition
Unit
Fac.Set
Description
P_83
Relay 01 Definition
3
RELAY-1 function selected from list
00
Fuel
01
Alarm
02
Start
03
Stop
04
Gen. Contactor
05
Mains Contactor
06
Choke
07
Preheat
08
Shutdown alarm
09
Shutdown or
load_dump alarm
10
Shutdown or
load_dump or warning
11
Automatic ready
12
-
13
-
14
Load_dump alarm
15
Fuel Main winding
16
Mains Fail
17
-
18
-
19
-
20
-
21
Flashing Relay
22
-
23
-
24
-
25
-
26
Idle Speed
27
-
28
-
29
-
30
-
31
-
32
Oil switch alarm
33
Temp switch alarm
34
-
35
-
36
-
37
-
38
Spare Alarm
39
-
40
Oil sender alarm
41
Temp sender alarm
42
Low speed alarm
43
High speed alarm
44
Low voltage alarm
45
High voltagealarm
46
Fail to start alarm
47
-
48
-
49
-
50
-
51
High battery voltage
alarm
52
Charge fail alarm
53
-
54
-
55
-
56
-
57
-
58
-
59
-
60
-
61
-
62
Spare load_dump
63
-
64
-
65
-
66
-
67
-
68
-
69
-
70
-
71
-
72
Overcurrent
load_dump
73
Excess power ldd
74
-
75
-
76
-
77
-
78
-
79
-
80
-
81
-
82
-
83
-
84
-
85
-
86
Spare warning
87
-
88
Oil sender warning
89
Temp sender warn.
90
Low speed warning
91
High speed warning
92
-
93
-
94
Fail to stop warning
95
-
96
Service request
warning
97
-
98
Low battery warning
99
High battery warning
100
Charge fail warning
101
-
102
-
103
-
104
Gen Low voltge warn.
105
Gen High voltge warn.
106
-
107
-
108
-
109
-
110
-
111
-
112
-
113
-
114
-
115
-
116
-
117
-
118
-
119
-