What to do if my Datalogic Card Reader is not transmitting to the host?
- JJeffery JonesAug 17, 2025
If the Datalogic Card Reader isn't transmitting data to the host, verify that the serial cable is correctly wired. If you're using a CBX, make sure the RS485 termination switch is OFF. Also, ensure that the host serial port settings match the reader's serial port settings. The "COM" LED in the VisiSet™ Digital I/O folder can be configured to indicate MAIN COM port TX or MAIN COM port RX.