EasyManua.ls Logo

DayTronic 3000PLUS - Page 44

DayTronic 3000PLUS
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3KP64 - 3.20
3000PLUS WITH 5D64 INSTRUCTION MANUAL V. SB.2
Daytronic Corporation
2211 Arbor Blvd. Dayton, OH 45439 (800) 668-4745
Tel: (937) 293-2566 Fax: (937) 293-2586 www.daytronic.com
SETUP STAGE 4(T): TWO-POINT CALIBRATION
When the
3000PLUS
displays this . . . Do this . . .
4(T).a. Before you can enter your first calibration point (ZERO POINT), you
must establish your transducer zero condition (less than 20% of full
scale). Normally, you would either remove all load from the source
transducer or apply a small but precisely known amount of load that is
to be continuously tared from the final measurement. When the trans-
ducer is fully unloaded, press
4(T).b. Use
and
as explained in Section 3.A to adjust the displayed number (if neces-
sary) to the desired
ZERO POINT OUTPUT READING, expressed in
measurement units. The number you enter here should be less than
20% of the
FULL-SCALE OUTPUT IN ENGINEERING UNITS which you
entered in Step 2.g.
Then press
If you have
not changed the displayed number (alternating with CAL 1)
via the
UP/DOWN buttons, you should proceed directly to entry of the
CAL 2 point in Step 4(T).c, below.
If, however, you have changed the displayed zero-point (
CAL 1) num-
ber, the 3000PLUS will calculate a new
MODULE INPUT OFFSET
(MIO)
, based on the entered reading, the current full-scale output set-
ting, and the
FULL-SCALE RANGE entered in Step 2.bsee Section 4.E
of this manual for more information on the
MIO parameter.
If this calculation yields an allowable offset value, that value will be
applied to the output, and you will see a display of
alternating with the
LIVE SCALED OUTPUT READING.
If the reading that is now displayed corresponds sufficiently to your
desired
ZERO POINT OUTPUT READING, press
and proceed to Step 4(T).c.
(contd)
ENTER
ENTER
ENTER
ST
and
CL
are lit.
3. FRONT-PANEL CONFIGURATION
AND CALIBRATION
alternating with the
LIVE SCALED
OUTPUT READING
(CHANNEL 1)*
* The 3000PLUS instruments MOD-
ULE INPUT OFFSET (MIO)
will be
automatically reset to 00.00
(zero) before the live output
reading is invoked. The previously
entered
CAL1 number may
appear for a second or two while
this occurs.

Related product manuals