EasyManua.ls Logo

DayTronic 3000PLUS - Front-Panel Setup Procedure

DayTronic 3000PLUS
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3KP64 - 3.35
3000PLUS WITH 5D64 INSTRUCTION MANUAL V. SB.2
Daytronic Corporation
2211 Arbor Blvd. Dayton, OH 45439 (800) 668-4745
Tel: (937) 293-2566 Fax: (937) 293-2586 www.daytronic.com
SETUP STAGE 7: VOLTAGE OUTPUT
When the
3000PLUS
displays this . . . Do this . . .
7.a. Press
7.b. The instruments current
FULL-SCALE VOLTAGE OUTPUTthat is, the
full-scale range of the scaled analog output (Channel 3)will be displayed:
5 V or 10 V. For rear-terminal connections involving the voltage output
(including 4-20 mA conversion), see Section 2.D.
Press
to toggle between the two allowed ranges. When the desired full-scale
output range is displayed, press
7.c. Press
7.d. The instruments current four-digit
SECURITY CODE will be displayed.*
This is the number (initially 0000) that must be entered in Step 1.b in
order to make changes to the instrument configuration via the front-panel
buttons.
If you do not want to change the displayed code, press
ENTER to exit the
front-panel setup procedure.
If you want to change the code number, use
and
as explained in Section 3.A to adjust the displayed number until the
desired security code is obtained (any number from 0000 through
9999).
Then press
to exit the front-panel setup procedure.
ENTER
ENTER
ENTER
SCROLL
ENTER
ST
and
AN
are lit.
3. FRONT-PANEL CONFIGURATION
AND CALIBRATION
FULL-SCALE
VOLTAGE OUTPUT
SELECTIONS:
5 V
10 V
* The SECURITY CODE will not be
displayed, however, when you are
in VIEW ONLY mode (see Steps
1.a through 1.d). In this mode,
pressing
ENTER after display of
the
FULL-SCALE VOLTAGE OUT-
PUT
parameter will cause you to
exit the setup display.

Related product manuals