Be sure the Vmax time delay
is set to 10 seconds.
Be sure that Vmax is set to
110%. Higher values may allow
overheating of internal motors.
Do not
adjust the voltage
monitor without explicit
instructions from Dectron.
When the branch circuit voltages
are correct, the green ON LED
should be on.
If it is not on, or is flashing, see
the following page for more
details.
Be sure the Vmin time delay
is set to 10 seconds.
Be sure that Vmin is set to 90%.
Lower values may allow
overheating of internal motors.
Do not
adjust the voltage
monitor without explicit instruc-
tions from Dectron.
Be sure that Ue is set to the
nominal voltage shown on the
Dectron nameplate.
Be sure the Ue time delay
is 5 seconds or less.
POOL # 1: ft² POOL # 3: ft²
E.W.T.: °F E.W.T.: °F
POOL # 2: ft² POOL # 4: ft²
E.W.T.: °F E.W.T.: °F
AIR TEMP.: °F R.H.: %
R-22 TOTAL SYSTEM CHARGE:
lbs
MAX. LENGTH OF REF. LINES (ONE WAY) ft