Dectron, Inc. March 2012
DSH/DSV/RSH/DBH/RBH Series Dehumidifier Owners Manual
T.A.B. Voltage Monitor
Data subject to change without notice.
190
DECTRON
105
80
85
90
95
0.1
0.1
0.1
5
5
5
10
10
10
15
15
15
20
20
20
110
115
Vmax (%Ue)
Vmin (%Ue)
Ue (VAC)
Delay (sec)
ON
Delay (sec)
Delay (sec)
Be sure the Vmax time delay
is set to 10 seconds.
Be sure that Vmax is set to
110%. Higher values may allow
overheating of internal motors.
Do not
adjust the voltage
monitor without explicit
instructions from Dectron.
When the branch circuit voltages
are correct, the green ON LED
should be on.
If it is not on, or is flashing, see
the following page for more
details.
Be sure the Vmin time delay
is set to 10 seconds.
Be sure that Vmin is set to 90%.
Lower values may allow
overheating of internal motors.
Do not
adjust the voltage
monitor without explicit instruc-
tions from Dectron.
Be sure that Ue is set to the
nominal voltage shown on the
Dectron nameplate.
Be sure the Ue time delay
is 5 seconds or less.
DRY-O-TRON ®
MODEL #:
SERIAL #:
I.D.
D
ELECTRICAL RATING
460 V ac, 3 ph, 60 Hz
COMPRESSOR
LRA RLA
COMPRESSOR
LRA RLA
COMPRESSOR
LRA RLA
COMPRESSOR
LRA RLA
BLOWER MOTOR HP FLA
BLOWER MOTOR HP FLA
BLOWER MOTOR HP FLA
COND. FAN MOTOR HP FLA
COND. FAN MOTOR HP FLA
PUMP MOTOR HP FLA
ENTHALPY MOTOR HP FLA
ELECTRIC HEATER kW A
Max. L.A.T. (°F)
SERVICE POWER
SPACE HEATING COIL
PSIG Max.
MCA A MAX. FUSE/CKT. BKR.*
15
A
*(HACR type per NEC)
R-22 FACTORY CHARGE
lbs
AIR VOLUME CFM
BELT SIZE
WIRING DIAGRAM
REFRIGERANT DESIGN PRESSURES: HIGH/LOW 300/150 PSIG
FABRIQUÉ AU CANADA / MADE IN CANADA
REF.:
POOL # 1: ft² POOL # 3: ft²
E.W.T.: °F E.W.T.: °F
POOL # 2: ft² POOL # 4: ft²
E.W.T.: °F E.W.T.: °F
AIR TEMP.: °F R.H.: %
R-22 TOTAL SYSTEM CHARGE:
lbs
MAX. LENGTH OF REF. LINES (ONE WAY) ft
BETWEEN D.O.T. & REMOTE CONDENSER:
LINE SIZE:
AIR COOLED COND. MODEL #:
HOT GAS: in
LIQUID: in
UNITS WITH TYPE 2 VOLTAGE MONITOR ONLY
T.A.B.
5.22

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dectron DRY-O-TRON Supervisaire DSV 020 and is the answer not in the manual?

Dectron DRY-O-TRON Supervisaire DSV 020 Specifications

General IconGeneral
BrandDectron
ModelDRY-O-TRON Supervisaire DSV 020
CategoryController
LanguageEnglish

Related product manuals