A/C ON - The Air-Conditioning feature is operating.
AIR HEATING CALL - The temperature of the room is below set point minus offset minus differential.
ASCT X ON
- The minimum OFF time for compressor X has not elapsed.
AUX. AIR HEATING ON STAGE 1
- First stage auxiliary air heating is ON.
AUX. AIR HEATING ON STAGE 2
- Second stage auxiliary air heating is ON.
AUX. AIR HEATING ON STAGE 3 - Third stage auxiliary air heating is ON.
AUX. AIR HEATING ON STAGE 4
- Fourth stage auxiliary air heating is ON.
BLOWER ON
- Blower is operating.
BLOWER REMOTE SWITCH OFF
- The blower is turned off by remote manual input.
BLOWER TURNED OFF - See Startup - Enable Operation.
COMPRESSOR X EMERGENCY SWITCH OFF - The manual ON/OFF switch is OFF.
COMPRESSOR X PUMPDOWN
- Compressor X is preparing to shut down.
COMPRESSOR X TURNED OFF - See Startup - Enable Operation.
COOLING CALL -
The temperature of the room is above set point plus offset plus
differential.
DEHUMIDIFICATION CALL - The relative humidity of the room is above set point plus differential.
DEHUMIDIFICATION ON
- One or more compressors are operating.
EVAPORATOR DAMPER CLOSED - The evaporator bypass damper is closed to divert air to the evaporator.
ECONOMIZER ON - The Economizer feature is operating.
GAS BOILER ON - The gas boiler on units so equipped is operating.
LEAD LAG ON - Compressor 2 is first stage.
MANUAL RESET REQUIRED -
A fatal alarm has occurred. See Operation - Start, Stop, Reset.
MAXIMUM EXHAUST BLOWER ON - The maximum amount of room air is being exhausted.
MINIMUM EXHAUST BLOWER ON - The standby amount of room air is being exhausted.
OCCUPIED PERIOD - Time-of-day is defined as that in which people are usually present.
OIL RETURN MODE X ON
- Refrigerant is being diverted through the outdoor condenser for oil return.
PLEASE WAIT... Compressor X will auto reset - A possibly fatal alarm is being analyzed.
POOL 1 AUX ON - An auxiliary heater is heating pool 1 water.
POOL 2 AUX ON - An auxiliary heater is heating pool 2 water.
POOL 1 HEATING CALL - The temperature of pool 1 water is below set point minus differential.
POOL 2 HEATING CALL - The temperature of pool 1 water is below set point minus differential.
POOL 1 HEATING ON - Water from pool 1 is being heated.
POOL 2 HEATING ON - Water from pool 2 is being heated.
PURGE MODE ON - Room air is being exhausted to dilute superchlorination gases.
VENTILATION ON
- Cooling or dehumidification by ventilation is enabled in the event of
compressor failure or no air-conditioning option.
ZERO REHEAT ON - Supply air temperature is limited to the return air temperature.
Check Status Enable Operation Startup
Dectron, Inc. March 2012
Owner’s Manual
DSH/DSV/RSH/DBH/RBH Series Dehumidifier
Data subject to change without notice.
231
STATUS MESSAGES
SCROLL DOWN
TO VIEW
Press
↓↓
repeatedly to view any of the following Status messages that apply at the moment.
NOTE: In the list below the letter “X” is a placeholder for a number referring to a particular refrigeration circuit. On
your screen the appropriate number will appear rather than the “X”.
STARTUP