Page 54 from 69
11. PQ Configuration
11.13 Values for PQ characteristics
PQ feature Parameter Setting range Devault value (EN 50160)
Voltage magnitude
Period 1 0 ... 100 % 95 %
Max. 1 +0.1 ... +25 % +10 %
Min. 1 -25 ... -0.1 % - 10 %
Period 2 0 ... 100 % 100 %
Max. 2 +0.1 ... +25 % +10 %
Min. 2 -25 ... -0.1 % - 15 %
Frequency
Period 1 0 ... 100 % 99.5 %
Max. 1 +0.1 ... +25 % +1 %
Min. 1 -25 ... -0.1 % -1 %
Period 2 0 ... 100 % 100 %
Max. 2 +0.1 ... +25 % +4 %
Min. 2 -25 ... -0.1 % -6 %
Flicker (long term)
Period 0 ... 100 % 95 %
Max. 0.2 ... 10 1,0
Flicker (short term)
Period 0 ... 100 % -
Max. 0.2 ... 10 -