Plug #8, AC current inputs
Term. Function Technical data Description
53 L1 s1 1 or 5 A AC Current phase L1
54 L1 s2
55 L2 s1 1 or 5 A AC Current phase L2
56 L2 s2
57 L3 s1 1 or 5 A AC Current phase L3
58 L3 s2
59 Not used
60
Plug #9, mains/busbar A AC voltage inputs
Term. Function Technical data Description
61 L 1 100 to 690 V AC Mains line 1 (AGC 244: BB A)
62 Not used
63 L 2 100 to 690 V AC Mains line 2 (AGC 244: BB A)
64 Not used
65 L 3 100 to 690 V AC Mains line 3 (AGC 244: BB A)
66 Not used
67 N Neutral
All AC voltage inputs are galvanically separated from the rest of the unit. Voltages are indica-
ted in phase-phase values.
Plug #10, busbar/busbar B AC voltage inputs
Term. Function Technical data Description
68 L 1 100 to 690 V AC Busbar line 1 (AGC 244: BB A)
69 Not used
70 L 2 100 to 690 V AC Busbar line 2 (AGC 244: BB A)
71 Not used
72 L 3 100 to 690 V AC Busbar line 3 (AGC 244: BB A)
73 Not used
74 N Neutral
75 Not used
76 Not used
All AC voltage inputs are galvanically separated from the rest of the unit. Voltages are indica-
ted in phase-phase values.