1-phase and 2-phase systems are also supported.
The application shown is for pulse breakers.
Be aware that the inputs for feedbacks shown above also need a common wire on terminal 91.
(Terminal 91 is common for 77 to 90).
5.2 DC connections
5.2.1 Digital inputs
Battery positive to input: Battery negative to input:
77
91 (COM.)
Switch
12/24V DC
Positive to input
77
91 (COM.)
Switch
12/24V DC
Negative to input
Emergency stop:
25
2 (-)
12/24V DC
Emergency stop
0V DC
5.2.2 Multi-inputs
The AGC 200 unit has three multi-inputs, which can be configured to be used as the following input types:
1. 4 to 20 mA
2. Pt100