5.3.3 CAN bus engine communication
AGC 200
CAN - L
13 14 15
GND
CAN - H
ECM
Engine Communication Module
CAN - L
CAN - H
RR
GND
CANbus port
R = 120ohms 1/4W
Shield ends must be insulated with tape or insulation tubing.
Use shielded twisted cable.
The terminating resistor at the engine side may not be needed if it is incorporated in the engine
controller. See the engine manufacturer’s literature.
5.3.4 External I/O module (option H8)
120
CAN H
CAN L
CANopen
CANopen
BECKHOFF
1 2 3 4 5 6 7 8
ON DIP
CAN A
CAN B
107
9 12
120
AGC 200
118
Gnd
AGC 200 installation instructions
4189340610 UK
Wirings