4.2.1 Display navigation
MAINS FAILURE
U-supply 24.1 V
G 0.001 PF 0 kW
G 0 kVA 0 kVAr
AGC 200
2010-01-06 08:59:08
MAINS FAILURE
P 0 kW 0 %
Q 0 kVAr 0 %
S 0 kVA 0 %
AGC 200
2010-01-06 08:59:08
Press
MAINS FAILURE
Event log
Alarm log
Battery test log
MAINS FAILURE
MAINS FAILURE
Wed Jan 06 13:36:23
MB OFF
Wed Jan 06 13:36:23
Press Press
Press
MAINS FAILURE
Setup menu
1000 G -P> 1
1010 G -P> 2
1030 G I> 1
1040 G I> 2
MAINS FAILURE
Setup menu
1000 Protection
2000 Synchronisation
2500 Regulation
3000 Binary input
MAINS FAILURE
1010 G -P> 1
Setpoint : -9.0 %
Timer : 10.2 s
Output A : Not used
Output B : Not used
Press Press
The scrollbar
indicates that more
readings are
available below
4.3 Controller setup
4.3.1 Controllers available
Governor (std.)
1. Synchronisation (static and dynamic sync.)
2. Phase angle (static sync.)
3. Frequency
4. Power
5. Load sharing
AVR (std.)
1. Voltage
2. Reactive power
3. Reactive load sharing
4. PF (CAP or IND)
4.3.2 Controller output types
CANbus engine communication (J1939/MTU MDEC or ADEC)
Analogue outputs require external I/O module IOM 200 series or option H8
Relays (std.)
Normally relays 28 to 34, but any configurable relay can be used
AGC 200 quick start guide 4189340608 UK
Display push-buttons and LEDs
DEIF A/S Page 19 of 21