Status text Condition Comment
---xx-------- >00< ------------ Generator is synchronising The "xx" marks the
actual generator
phase angle position
in the synchronisa-
tion. When the "xx" is
aligned over the 00
centre, the generator
is in synchronism
TOO SLOW 00<------------- Generator running too slow during synchronising
-----------> 00 TOO FAST Generator running too fast during synchronising
EXT. START ORDER A planned AMF sequence is activated There is no failure on
the mains during this
sequence
SELECT GENSET MODE Power management has been deactivated and no
other genset mode has been selected
Option G5 must be
available
QUICK SETUP ERROR Quick setup of the application failed
MOUNT CAN CONNEC-
TOR
Connect the power management CAN line
ADAPT IN PROGRESS The AGC 200 is receiving the application, to which it
has just been connected
SETUP IN PROGRESS The new AGC is being added to the existing applica-
tion
SETUP COMPLETED Successful update of the application in all AGC units
REMOVE CAN CONNEC-
TOR
Remove the power management CAN lines
RAMP TO #####kW The power ramp is ramping in steps, and the next
step that will be reached after the timer has expired
will be displayed
DERATED TO #####kW Displays the ramp-down set point
UNEXPECTED GB ON BB Another generator breaker is closed on to the bus-
bar (due to a GB position failure) while no voltage is
present on the busbar
This indicates that
other breakers can-
not close to the bus-
bar because of posi-
tion failure on one or
more GBs
WARM UP RAMP Warm up ramp is active The available power
is limited until the
predefined tempera-
ture is reached or
when the input which
activated warm up
ramp is set low
AGC 200 operators manual 4189340607