3. The first steps
3.1 Switching on the first time
3.1.1 Terminals
The dashed lines in the diagram below show the most important terminals to use in order to get started. Once
all connections to the unit are made, the unit is ready to be switched on.
6 7 83 4 51 2
+ -
Power
supply
Status
Multi-functional
inputs
Com
Generator voltage
33 34 35 36 37 38
L1 N L2 L3NA NA
10 11 12 13 14 15 16 1817
Binary inputs
20 21 22 24 2523 26 27
Mains voltage
28 29 30 31 32
L1 N L2 L3NA
45 46 47 48
L1 L2 L3
Generator current
39 40 41 42 43 44
MPU
Com
W/L
RPM inputs
GB MB
USB
Emer.
stop
58 59
Relays
RS485
Modbus
55
54
53
B(-)
GND
A(+)
CAN J1939
50
49
CAN H
CAN L
51
GND
s1 s2 s1 s2 s1 s2
56 57
Start prepare
Starter (Crank)
Run coil
For further wiring information, please refer to the Installation Instructions.
3.2 Configuration and connection
3.2.1 Configuration
Many parameters in the controller can be configured from the display, but when changing inputs, outputs, M-
Logic, etc., it is necessary to use the PC utility software 3. This can be downloaded free of charge from
www.deif.com.
CGC 400 quick start guide 4189340849 UK
The first steps
DEIF A/S Page 6 of 10