GPC, PPU Option O1, Water turbine control
DEIF A/S Page 19 of 19
4. Parameter list
2250 Turbine start
No. Setting Min. setting Max. setting Factory
setting
2255 Turbine start timer Time 0 s 100 s 0 s
3520 4-20mA in. no 5.1
No. Setting Min. setting Max. setting Factory
setting
3521 4-20mA in no. 5.1 Set point 0.0% 250.0% 10.0%
3522 4-20mA in no. 5.1 Time 0.2 s 100.0 s 10.0 s
3523 4-20mA in no. 5.1 Relay output A R0 (none) R2
3524 4-20mA in no. 5.1 Relay output B R0 (none)
Option
dependent
R0
3525 4-20mA in no. 5.1 Enable OFF ON OFF
3530 4-20mA in. no 5.2
No. Setting Min. setting Max. setting Factory
setting
3531 4-20mA in no. 5.2 Set point 0.0% 250.0% 10%
3532 4-20mA in no. 5.2 Time 0.2 s 100.0 s 10.0 s
3533 4-20mA in no. 5.2 Relay output A R0 (none) R2
3534 4-20mA in no. 5.2 Relay output B R0 (none)
Option
dependent
R0
3535 4-20mA in no. 5.2 Enable OFF ON OFF
4040 Power settings
No. Setting Min. setting Max. setting Factory
setting
4041 Controller settings P Fixed power set point
0% 100% 100%
4042 Controller settings
var
Fixed var set point 0% 100% 30%
4043 Controller settings
PF
Fixed PF set point
0.60 1.00 0.90
4044 Controller settings W
Water level nominal 0% 250% 100%
4045 Controller settings
Wmin
Water level min.
-100% 250% 0%
4130 Water level indication
No. Setting Min. setting Max. setting Factory
setting
4131 Water level in. Enable OFF ON OFF
DEIF A/S reserves the right to change any of the above