Site preparations
The N3200-ON Series switch is suitable for installation as part of a common bond network (CBN).
You can install the switch in:
Network telecommunication facilities
Data centers
Other locations where the National Electric Code (NEC) applies
NOTE: Install the switch into a rack or cabinet before installing any additional components such as cables or optics.
Topics:
Site selection
Cabinet placement
Rack mounting
Switch ground
Fans and airflow
Power
Storing components
Site selection
Install the switch equipment in restricted access areas.
A restricted access area is one in which service personnel can only gain access using a special tool, lock, key or other means of
security. The authority responsible for the location controls access to the restricted area.
Ensure that the area where you install your switch meets the following safety requirements:
Near an adequate power source. Connect the switch to the appropriate branch circuit protection according to your local
electrical codes.
Switch environmental temperature is from 32° to 113°F (0° to 45°C).
Relative humidity is from 5 to 95 percent (RH), noncondensing.
In a dry, clean, well-ventilated, and temperature-controlled room, away from heat sources such as hot air vents or direct
sunlight
Away from sources of severe electromagnetic noise.
Inside the restricted access area, which is positioned in a rack or cabinet, or on a desktop with adequate space in the front,
back, and sides for proper ventilation and access
Install the switch in Information Technology Rooms in accordance with Article 645 of the National Electrical Code and NFPA
75.
For more information about switch storage and environmental temperatures, see Specifications.
Cabinet placement
Install the N3200-ON Series switch only in indoor cabinets that are designed for use in a controlled environment.
Do not install the switch in cabinets that are outdoors. For cabinet placement requirements, see Site selection.
The cabinet must meet minimum size requirements. Airflow must be in accordance with the Electronic Industries Alliance (EIA)
standard. Ensure that there is a minimum of 12.7 cm (5 inches) between the intake and exhaust vents and the cabinet wall.
3
Site preparations 21

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dell EMC PowerSwitch N3224F-ON and is the answer not in the manual?

Dell EMC PowerSwitch N3224F-ON Specifications

General IconGeneral
BrandDell EMC
ModelPowerSwitch N3224F-ON
CategorySwitch
LanguageEnglish

Related product manuals