Table 11 DPE power requirements, per model
Specification Unity 480/480F Unity 680/680F Unity880/880F
AC line voltage 100 to 240 VAC
± 10%, single phase,
47 to 63 Hz
100 to 240 VAC
± 10%, single phase,
47 to 63 Hz
100 to 240 VAC
± 10%, single phase,
47 to 63 Hz
AC line current
(operating maximum)
10.6 A max at 100
VAC; 5.3 A max at
200VAC
11.72 A max at 100
VAC; 5.86 A max at
200VAC
14.41 A max at 100
VAC; 7.2 A max at
200VAC
Power consumption
(operating maximum)
1060 VA (1050W)
max at 100 VAC; 1060
VA (1050 W) max at
200 VAC
1172 VA (1161 W) max
at 100 VAC; 1172 VA
(1161 W) max at 200
VAC
1440.77 VA (1411.96)
max at 100 VAC;
1440.77 VA (1411.96
W) max at 200 VAC
Power factor 0.95 minimum at full
load, @ 100/ 200 VAC
0.95 minimum at full
load, @ 100/ 200 VAC
0.95 minimum at full
load, @ 100/ 200 VAC
Heat dissipation
(operating maximum)
3.78 x 10
6
J/hr,
(3,581 Btu/hr) max at
100 VAC; 3.78 x 10
6
J/hr, (3,581 Btu/hr)
max 200VAC
4.18 x 10
6
J/hr,
(3,960 Btu/hr) max
at 100 VAC; 4.18 x 10
6
J/hr, (3,960 Btu/hr)
max 200VAC
5.08 x 10
6
J/hr,
(4,818 Btu/hr) max at
100 VAC; 5.08 x 10
6
J/hr, (4,818 Btu/hr)
max 200VAC
In-rush current 45 Apk cold per line
cord, at any line
voltage
45 Apk cold per line
cord, at any line
voltage
45 Apk cold per line
cord, at any line
voltage
Startup surge current 120 Apk hot per line
cord, at any line
voltage
120 Apk hot per line
cord, at any line
voltage
120 Apk hot per line
cord, at any line
voltage
AC protection 20 A fuse on each
power supply, single
line
20 A fuse on each
power supply, single
line
20 A fuse on each
power supply, single
line
AC inlet type (high
line power)
IEC320-C14 appliance
coupler, per power
zone
IEC320-C14 appliance
coupler, per power
zone
IEC320-C14 appliance
coupler, per power
zone
AC inlet type (low line
power)
IEC320-C20
appliance coupler, per
power zone
IEC320-C20
appliance coupler, per
power zone
IEC320-C20
appliance coupler, per
power zone
Ride-through sharing 10 ms min 10 ms min 10 ms min
Current sharing ± 5 percent of full
load, between power
supplies
± 5 percent of full
load, between power
supplies
± 5 percent of full
load, between power
supplies
Operating environment requirements
Temperature gradient and altitude requirements
Systems and components must not experience changes in temperature and humidity
that are likely to cause condensation to form on or in that system or component. Do
not exceed the temperature gradient of 20°C/hr (36°F/hr), or the altitude
requirement of 3050 m (10,0000 ft).
Technical specifications
22 Unity 480/F, Unity 680/F, Unity 880/F Hardware Information Guide