Dell PowerEdge R830 - Particulate and Gaseous Contamination Specifications

Dell PowerEdge R830
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 20. Maximum altitude specications
Maximum altitude Specications
Operating
3048 m (10,000 ft)
Storage 12,000 m (39,370 ft)
Table 21. Operating temperature de-rating specications
Operating temperature de-rating Specications
Up to 35°C (95°F) Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950
m (3,117 ft).
35°C to 40°C (95°F to 104°F) Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above 950
m (3,117 ft).
40°C to 45°C (104°F to 113°F) Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above 950
m (3,117 ft).
Related links
Expanded operating temperature
Particulate and gaseous contamination specications
The following table denes the limitations that help avoid any equipment damage or failure from particulates and gaseous
contamination. If the levels of particulates or gaseous pollution exceed the specied limitations and result in equipment damage or
failure, you may need to rectify the environmental conditions. Re-mediation of environmental conditions is the responsibility of the
customer.
Table 22. Particulate contamination specications
Particulate contamination Specications
Air ltration Data center air ltration as dened by ISO Class 8 per ISO 14644-1 with a
95% upper condence limit.
NOTE: This condition applies to data center environments only.
Air ltration requirements do not apply to IT equipment designed
to be used outside a data center, in environments such as an
oce or factory oor.
NOTE: Air entering the data center must have MERV11 or
MERV13 ltration.
Conductive dust Air must be free of conductive dust, zinc whiskers, or other conductive
particles.
NOTE: This condition applies to data center and non-data center
environments.
Corrosive dust
Air must be free of corrosive dust.
Residual dust present in the air must have a deliquescent point less
than 60% relative humidity.
NOTE: This condition applies to data center and non-data center
environments.