OUTPUT CONFIGURATION 2: AV22 (refer to page 30, and associated Application
information)
OUTPUT CONFIGURATION 3: AV23 (refer to page 30, and associated Application
information)
ADDITIONAL PARAMETERS: AV24 to AV29 (as per associated Application information)
Control Settings
These are other settings you may want to set from the OWS, which may also be commanded on the fly
by a user or from a GCL+ program:
ALGORITHM MODE: AV13 (which defaults to Night)
DAY SETPOINT: AV6
DAY MINIMUM: AV7
DAY MAXIMUM: AV8
DAY DIFFERENTIAL: AV9
NIGHT HEAT SETPOINT: AV10 (which can only be changed remotely, not via the keypad)
NIGHT COOL SETPOINT: AV11 (which can only be changed remotely, not via the
keypad)
Additional Settings
These are additional settings you may also want to set from the OWS, and may be commanded as
necessary, but rarely are once they have been set (or the control loop has been tuned).
PROPORTIONAL BAND: AV19
RESET RATE: AV20
DISPLAY CODE: AV15 (refer to page 5)
PIN ACCESS CODE: AV31 (which can only be changed remotely, not via the keypad)
SERVICE TOOL MODE: AV32 (to enable or disable access)
AI2 (AND AI3) CONFIGURATION
While AI1 is typically configured from the Configuration Menu, by setting the Temperature Units
setting (degrees C or F), additional inputs such as AI2 (and AI3 on the DNT-T221) are configured
through the OWS. Once you have ensured that the input is correctly wired and the hardware jumper is
appropriately set, use ORCAview to verify that the AI object is not in manual mode and the units are
properly set for the sensor. An exception to this is if AI2 is used for VAV airflow – setting the
application will configure AI2 accordingly.
COPYING THE CONFIGURATION FROM ONE DEVICE TO ANOTHER
It is possible to copy the configuration setup of one BACstat to another. It is a simple 1-2-3 procedure:
1. Configure one BACstat for the desired application with the settings you want.
2. Save the BACstat settings to a file on ORCAview (as described below, under Save As).
3. Load this file into the other BACstats on the network, one at a time.
This should replicate the same configuration (i.e., object values) from one BACstat to another, and
provide you a backup copy of the configuration settings in a file. The BACstat that you are copying the
configuration to must have its application set either to NONE or to the exact same application as the
saved setup.