Chapter 4 Parameters|
4-4 Revision May 2008, ME14, SW V3.04
Parameter Explanation Settings
Factory
Setting
Customer
Pr.30
DC Braking during
Stopping
0.0 to 25.0 sec
0.0
Pr.31
Start-point for DC
Braking
0.00 to 60.00 Hz
0.00
Pr.32
Momentary Power
Loss Operation
Selection
00: Stop operation after momentary power
loss
01: Continues after momentary power loss,
speed search starts with Master
Frequency
02: Continues after momentary power loss,
speed search starts with Minimum output
Frequency
00
Pr.33
Maximum Allowable
Power Loss Time
0.3 to 5.0 sec
2.0
Pr.34
Base-Block Time for
Speed Search
0.3 to 5.0 sec
0.5
Pr.35
Maximum Current
Level for Speed
Search
30 to 200 %
150
Pr.36
Upper Bound of
Output Frequency
0.10 Hz to 400.0 Hz
400.0
Pr.37
Lower Bound of
Output Frequency
0.00 Hz to 400.0 Hz
0.00
Pr.38
Multi-function Input
Terminal (M0,M1)
00: M0: FWD/STOP, M1: REV/STOP
01: M0: RUN/STOP, M1: REV/FWD
02: M0, M1, M2: 3-wire operation control
mode
00
Pr.39
Multi-function Input
Terminal (M2)
05
Pr.40
Multi-function Input
Terminal (M3)
06
Pr.41
Multi-function Input
Terminal (M4)
07
Pr.42
Multi-function Input
Terminal (M5)
00: No Function
01: Output OFF (N.O.) (enabled when
running)
02: Output OFF (N.C.) (enabled when
running)
03: External Fault (normally open) N.O.
04: External Fault (normally close) N.C
05: RESET
06: Multi-Step Speed Command 1
07: Multi-Step Speed Command 2
08: Multi-Step Speed Command 3
09: Jog Operation
10: Accel/Decel Speed Inhibit
11: First or Second Accel/Decel Time
12: Base-block (B.B.) (N.O)
08