Chapter 4 Parameters|   
Revision May 2008, ME14, SW V3.04  4-37
Settings  Function  Description 
14 
Increase Master 
Frequency  
15 
Decrease Master 
Frequency  
Parameter values 14, 15 program the Multi-Function Input 
Terminals: M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or 
M5 (Pr.42) to incrementally increase/ decrease the Master 
Frequency each time an input is received.  
 
GND
setting by 14
setting by 15
Mx "Close": Freq. will increase 
      by one unit.
Mx "Open":Freq. will decrease 
      by one unit.
UP
DOWN
 
16  Run PLC Program 
17 Pause PLC Program 
Parameter value 16 programs Multi-Function Input Terminal: 
M1 (Pr.38), M2 (Pr.39), M3 (Pr.40), M4 (Pr.41) or M5 (Pr.42) 
to enable the AC drive internal PLC program.  Parameter 
value 17 programs an input terminal to pause the PLC 
program. 
 
GND
setting by 16
setting by 17
Mx "Close": Run PLC.
Mx "Open":Pause PLC.
PLC operation
 
 
 Note: Pr.17 to Pr.23, Pr.78, Pr. 79, Pr.81 to Pr.87 define the 
PLC program. Another related function is “30 One-Shot 
PLC Run”. It can be set to use a not-latched contact as 
the run signal.