Chapter 2 Specifications and System Configuration
2-74
2_
AS-FCOPM
With its own standalone communication port, the extension card can work independently and can be set as a
slave or a master node. After installing the extension card, go to the HWCONFIG in ISPSoft to set up the
communication.
Wiring example
GND
CAN_H CAN_L
Master node
Slave node
Slave node
Terminal
resistor
(120 ohm)
Shielded
cable
GND
CAN_H CAN_L
GND
CAN_H CAN_L
Terminal
resistor
(120 ohm)
AS-F422
You can use this extension card for communication with Delta HMI series or other devices through the RS-422
communication port. The Communication functions are the same as the built-in ones. You can set the
communication port as a slave or a master node. After installing the extension card, go to the HWCONFIG in
ISPSoft to set up communication.
Wiring example of the communication with Delta HMI DOPA series via COM2
3
4
1
2
6
7
8
9
COM2/DB-9
AS-F422
Delta HMI seriesDOPA
2
1
3
4
T+
T-
R+
R-
Rx+
Rx-
Tx+
Tx-
RTS-
RTS+
CTS+
CTS-
AS-F485
With its own standalone communication port, the extension card can work independently and can be set as a
slave or a master node. After installing the extension card, go to the HWCONFIG in ISPSoft to set up
communication.
Wiring example
D+ D-
SG D+ D- SG SG D+ D-
Master node
Slave node Slave node
Shielded
cable
Shielded
cable
Terminal
resistor
(120 ohm)
Terminal
resistor
(120 ohm)

Table of Contents