Chapter 9 Ethernet Specification and Operation
9-83
9_
*2 Interface Capability Flags
Bit Description
0 BOOTP Client
1 DNS Client
2 DHCP Client
3 DHCP-DNS Update
4 Configuration Settable
5 Hardware Configurable
6 Interface Configuration Change Requires Reset
*3 Interface Configuration Control
Status Description
0
The device uses the interface configuration values previously stored (for example, in non-volatile
memory or through hardware switches).
1 The device obtains its interface configuration values through BOOTP.
2 The device obtains its interface configuration values through DHCP on start-up.
9.8.9 Ethernet Link Object (Class ID: F6 Hex)
This object maintains link-specific counters and status information for an IEEE 802.3 communications interface.
Service Code
Service
Code
Service Name
Support
Description
Class Attribute Instance Attribute
H’01 Get_Attributes_All X V Read all attributes
H’0E Get_Attributes_Single V V Read one attribute
Class
Class ID: H’F6

Table of Contents