AS Series Operation Manual
9-60
_9
Click Change if you need to make a change to the module definition.
Modify the module definition
1) Name: Click the arrow button to select a valid connection.
2) Size: Rockwell PLC supports maximum 500 bytes data size. (Data for input contains 2 bytes of Serial Number
and for output contains 4 bytes 32-bit Run-idle header and 2 bytes of Serial Number.) If using AS300, you can set
the maximum data length 498 SINT for input and 494 SINT for output.
In general, there is no need to change the parameters from the imported EDS files which can usually be used
without modification.