Chapter 2 Specifications and System Configuration
2-36
2_
Functional specifications
Digital-to-analog
conversion
Voltage output
Rated output
range
±10 V 0 V10 V ±5 V 0 V5 V 1 V5 V
Conversion
Range
K-32000
~
K+32000
K0 ~ K32000
K-32000
~
K+32000
K0 ~ K32000 K0 ~ K32000
Hardware output
range
-10.1V to
+10.1V
-0.1V to +10.1V
-5.05V to
+5.05V
-0.05V to
+5.05V
0.95V5.05V
Error rate (Room
temperature)
±0.2%
Error rate (Full
temperature
range)
±0. 5%
Linearity error
(Room
temperature)
±0.05%
Linearity error
(Full temperature
range)
±0.05%
Hardware
resolution
12 bits
Input impedance
1 k Ω 500 Ω
Digital-to-analog
conversion
Current output
Rated output
range
0 mA20 mA 4 mA20 mA
Conversion
Range
K0 ~ K32000 K0 ~ K32000
Hardware output
range
-0.2 mA to +20.2 mA 3.8 mA20.2 mA
Error rate (Room
temperature)
±0.2%
Error rate (Full
temperature
range)
±0.5%
Linearity error
(Room
temperature) (
Full
temperature
range)
±0.03%
Linearity error
±0.03%
Hardware
resolution
12 bits
Input impedance
550 Ω