EasyManuals Logo

Delta ASD-A2-1021 Series User Manual

Delta ASD-A2-1021 Series
721 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #557 background imageLoading...
Page #557 background image
ASDA-A2 Chapter 9 Communications
9-12 Revision February, 2017
Before and after the transmission in RTU mode, 10ms of silent interval is needed.
Example 3: function code 10H, write multiple words:
The Master issues command to the 1
st
Slave and writes 0BB8H and 0000H to the starting address
0112H. That is to say, 0112H is written into 0BB8H and 0113H is written into 0000H. The
maximum allowable data in one single access is 10. The Slave sends the response message to
the Master after the writing is completed. The calculation of LRC and CRC will be described in next
chapter.
ASCII Mode:
Command message (Master): Response message (Slave):
Start ‘:’ Start ‘:’
Slave Address
‘0’
Slave Address
‘0’
‘1’ ‘1’
Function
‘1’
Function
‘1’
‘0’ ‘0’
Starting data
address
‘0’
Starting data
address
‘0’
‘1’ ‘1'
‘1’ ‘1’
‘2’ ‘2’
Number of data
(In Word)
‘0’
Number of data
‘0’
‘0’ ‘0’
‘0’ ‘0’
‘2’ ‘2’
Number of data
(In Byte)
‘0’
LRC Check
‘D’
‘4’ ‘A’
The first data
content
‘0’
End 1 (0DH)(CR)
‘B’ End 0 (0AH)(LF)
‘B’
‘8’
The second data
content
‘0’
‘0’
‘0’
‘0’
LRC Check
‘1’
‘3’
End 1 (0DH)(CR)
End 0 (0AH)(LF)

Table of Contents

Other manuals for Delta ASD-A2-1021 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ASD-A2-1021 Series and is the answer not in the manual?

Delta ASD-A2-1021 Series Specifications

General IconGeneral
BrandDelta
ModelASD-A2-1021 Series
CategoryServo Drives
LanguageEnglish

Related product manuals