M
michelle42Aug 27, 2025
How to solve DSP firmware upgrade issue on Delta Servo Drives?
- NnunezcharlesAug 27, 2025
To solve a DSP firmware upgrade issue on Delta Servo Drives, set P2-08 to 30 first, and then 28 next, and restart the servo drive.
How to solve DSP firmware upgrade issue on Delta Servo Drives?
To solve a DSP firmware upgrade issue on Delta Servo Drives, set P2-08 to 30 first, and then 28 next, and restart the servo drive.
What is motor protection error on Delta ASD-A2-5543?
A motor protection error on Delta Servo Drives means that the setting value of parameter P1-57 is reached after a period of time set by parameter P1-58. Set P1-57 to 0. Correctly set P1-57 and P1-58.
What does pre-overload warning mean for Delta ASD-A2-5543 Servo Drives?
A pre-overload warning for Delta Servo Drives means that the drive is going to overload. Please refer to the correction actions of AL006. Increase the setting value of P1-56 or set P1-56 to 100 and above.
What does input power phase loss mean for Delta Servo Drives?
If your Delta Servo Drive is experiencing input power phase loss, it indicates that the control power supply is in error. If the fault persists even when the three-phase power is connected correctly, please contact your distributor or Delta for assistance.
What does it mean when my Delta Servo Drive has a memory error?
A memory error on your Delta Servo Drive can occur due to: * Parameter data error when writing into EE-PROM. If this is the case, correct the setting value of the parameter to clear the fault and restart the servo drive. * The setting value of a hidden parameter is in error. If this fault occurs when resetting the parameter settings, it indicates that the servo drive type is not set correctly. Correctly set the servo drive type again. * Data in EE-PROM is damaged. If this is the case, please contact your distributor or Delta for assistance.
What causes IGBT temperature error in Delta ASD-A2-5543 Servo Drives?
An IGBT temperature error in Delta Servo Drives can occur if: * The drive has exceeded its rated load during continuous operation. If this is the case, increase motor capacity or reduce load. * There is a short-circuit at the drive output. If this is the case, ensure all wiring is correct.
What causes excessive deviation in Delta ASD-A2-5543?
Excessive deviation in Delta Servo Drives can be caused by: * Maximum deviation parameter setting is too small. If this is the case, increase the parameter setting value of P2-35. * Gain value is too small. If this is the case, correctly adjust gain value. * Torque limit is too low. If this is the case, correctly adjust torque limit value. * There is an overload. If this is the case, reduce external applied load or re-estimate the motor capacity.
How to fix an overload error on Delta ASD-A2-5543?
An overload error on your Delta Servo Drive indicates that the drive has exceeded its rated load during continuous operation or that control system parameter setting is incorrect or that the wiring of drive and encoder is in error or that the encoder of the motor is damaged. To resolve this issue: * Increase motor capacity or reduce the load. * Adjust the gain value of the control circuit or decrease Accel/Decel time setting. * Ensure all wiring is correct. * If the encoder of the motor is damaged, please contact your distributor for assistance or contact with Delta.
What to do if data range error occurs when accessing CANopen object on Delta ASD-A2-5543?
If the data in the message has exceeded the data range of the specified object, NMT Maser send “Reset node“ command to its slave or reset the fault by sending the control word (0x6040) through CAN communication (the value of CANopen object 0x6040 should be reset).
What to do if CANopen SDO receive buffer overrun occurs on Delta Servo Drives?
If a CANopen SDO receive buffer overrun is detected (receive two or more SDO packets in 1ms), NMT Maser send “Reset node“ command to its slave or reset the fault by sending the control word (0x6040) through CAN communication (the value of CANopen object 0x6040 should be reset).