Chapter 8 ParametersASDA-A2R Series
8-266 Revision December, 2014
Settings
When PM-03.Y = 0, motor will detect motor magnetic field
automatically when applying to the power. The amount of
current is the same as the setting value. Followings are the
adjusting condition:
1. When the motor friction is too excessive, it easily cause
AL.052 duing to the wrong detection of magnetic field.
Increase the value can reduce the occurrence of Alarm
52.
2. During the magnetic field detection, if the vibration is too
excessive, reduce the value of this parameter could reduce
the vibration.
Please note that the magnetic field detection does not work
if Z axis has no spring or balance.
PM-12
Condition of Magnetic Field Detection
When Power On
Address:
Applicable
motor type
ALL
Related Section: -
Operational
Interface
Panel / Software Communication
Default
100
Unit
N/A
Range
0X00 ~ 0XFF
Data Size
16bit
Format
HEX
Settings
X:
If the moving of motor magnetic field is more than X*0.25
degrees, the condition is established.
Y:
If the motor magnetic field should move more than Y*10
degrees, the condition is established.
When condition X and Y are both established, the detection of
motor magnetic field succeed.
When condition X or Y is not established, it will detect the
magnetic field by different angle. When the detection is failed
up to four times, AL.052 will occur.
PM-13
Reserved Address:

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta ASD-A2R-0221 Series and is the answer not in the manual?

Delta ASD-A2R-0221 Series Specifications

General IconGeneral
BrandDelta
ModelASD-A2R-0221 Series
CategoryServo Drives
LanguageEnglish

Related product manuals